EasyManua.ls Logo

Siemens 7SJ85 - Application and Setting Notes

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application and Setting Notes
Time Synchronization
In order to ensure the time accuracy of the PMU, you must select IRIG-B as protocol for the GPS clock, see the
following figure. With other settings, the PMU function function group indicates that it is not time synchron-
ized.
[sc_setting time source_2014-09-09, 1, en_US]
Figure 10-23
Setting Time Synchronization
To detect a lack of synchronization quickly, also set the waiting time for the failure indication of the loss of
time synchronization to the smallest possible value, thus to 1 s.
Parameter: Mode
Default setting (_:10621:1) Mode = on
Activate and deactivate the PMU or switch to Test mode via the parameter Mode. The possible setting values
are on, off and test. In Test mode, the PMU data is marked as invalid.
Parameter: Reporting rate
Default setting (_:10621:102) Reporting rate = 10 frames/s
With the parameter Reporting rate, you specify the number of telegrams that are compiled and sent to
the PDC per second.
i
i
NOTE
Different setting values are shown or hidden, depending on the rated frequency set.
10.9.8
Measured Values, Energy Values, and Supervision of the Primary System
10.9 Phasor Measurement Unit (PMU)
SIPROTEC 5, Overcurrent Protection, Manual 1343
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals