EasyManua.ls Logo

Siemens 7SJ85 - Circuit-Breaker Wear Monitoring

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Circuit-Breaker Wear Monitoring
Setting Values
Threshold value
ΣI
x
-method stage
0 to 10 000 000 Increments of 1
2P-method stage 0 to 10 000 000 Increments of 1
I
2
t-method stage
0.00 I/Ir*s to 21 400 000.00 I/Ir*s Increments of 0.01
CB opening time 0.001 s to 0.500 s Increments of 0.001 s
CB break time 0.001 s to 0.600 s Increments of 0.001 s
CB make time 0.001 s to 0.600 s Increments of 0.001 s
Exponent for the ΣI
x
method
1.0 to 3.0 Increments of 0.1
Switching cycles at I
rated
100 to 1 000 000 Increments of 1
Rated short-circuit breaking current I
sc
10 to 100 000 Increments of 1
Switching cycles at I
sc
1 to 1000 Increments of 1
Level of warning 1 1 % to 100 % Increments of 1 %
Level of warning 2 1 % to 100 % Increments of 1 %
Operating current
threshold
1 A @ 50 and 100
Irated
0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100
Irated
0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Delay correction time -0.050 s to 0.050 s Increments of 0.001 s
Tolerances
Tolerance of the measured value make time
± 2 ms
12.73
Technical Data
12.73 Circuit-Breaker Wear Monitoring
SIPROTEC 5, Overcurrent Protection, Manual 1571
C53000-G5040-C017-8, Edition 07.2017