EasyManua.ls Logo

Siemens 7SJ85 - Current-Balance Supervision

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Current-Balance Supervision
Setting Values
Release threshold 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
1 A @ 50 Irated
5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
5 A @ 50 Irated
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold value min/max 0.10 to 0.95 Increments of 0.01
Tripping delay 0.00 s to 100.00 s Increments of 0.01 s
Dropout Ratio
Overcurrent dropout ratio Approx. 0.97
Undercurrent dropout ratio Approx. 1.05
Times
Tripping time Approx. 500 ms
Dropout time Approx. 500 ms
12.59
Technical Data
12.59 Current-Balance Supervision
SIPROTEC 5, Overcurrent Protection, Manual 1553
C53000-G5040-C017-8, Edition 07.2017

Table of Contents