Parameter: Minimum pulse length
•
Default setting (_:102) Minimum pulse length = 0.10 s
With the parameter Minimum pulse length, you specify a consistent minimum size for the output indica-
tion
Pulse
.
Settings
Addr. Parameter C Setting Options Default Setting
I-jump det. #
_:1 I-jump det. #:Mode
•
off
•
on
•
test
off
_:9 I-jump det. #:Measured
value
•
phase currents
•
zero-sequence current
phase currents
_:101 I-jump det. #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:101 I-jump det. #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:102 I-jump det. #:Minimum
pulse length
0.01 s to 60.00 s 0.10 s
Information List
No.
Information Data Class
(Type)
Type
I-jump det. #
_:81 I-jump det. #:>Block stage SPS I
_:501 I-jump det. #:>Pulse extension SPS I
_:54 I-jump det. #:Inactive SPS O
_:52 I-jump det. #:Behavior ENS O
_:53 I-jump det. #:Health ENS O
_:301 I-jump det. #:Jump ACT O
_:302 I-jump det. #:Pulse ACT O
6.49.5
6.49.6
Protection and Automation Functions
6.49 Current-Jump Detection