IN Measured
The function operates with the measured ground current IN. This is the
recommended setting unless there is a specific reason to use the calculated
zero-sequence current 3I0.
3I0 Calculated
The function operates with the calculated zero sequence current 3I0. This
setting option can be used when applying a redundant 50N/51N function for
safety reasons.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:9 General:Measured
value
•
3I0 calculated
•
IN measured
IN measured
6.5.3.3
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
SIPROTEC 5, Overcurrent Protection, Manual 381
C53000-G5040-C017-8, Edition 07.2017