Addr. Parameter C Setting Options Default Setting
_:101 Y0> G0/B0 #:3I0>
release thresh. value
1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:103 Y0> G0/B0 #:V0>
threshold value
0.300 V to 200.000 V 30.000 V
_:104 Y0> G0/B0 #:Dir. deter-
mination delay
0.00 s to 60.00 s 0.10 s
_:6 Y0> G0/B0 #:Operate
delay
0.00 s to 60.00 s 2.00 s
Information List
No. Information Data Class
(Type)
Type
Y0> G0/B0 #
_:81 Y0> G0/B0 #:>Block stage SPS I
_:501 Y0> G0/B0 #:>Block delay & op. SPS I
_:54 Y0> G0/B0 #:Inactive SPS O
_:52 Y0> G0/B0 #:Behavior ENS O
_:53 Y0> G0/B0 #:Health ENS O
_:60 Y0> G0/B0 #:Inrush blocks operate ACT O
_:55 Y0> G0/B0 #:Pickup ACD O
_:56 Y0> G0/B0 #:Operate delay expired ACT O
_:57 Y0> G0/B0 #:Operate ACT O
Directional Stage with Phasor Measurement of a Harmonic
Description
The Directional stage with phasor measurement of a harmonic is based on a continuous measuring direc-
tion-determination method. The stage determines the direction via the 3rd, 5th, or 7th harmonic phasors of
the zero-sequence voltage V0 and current 3I0.
6.15.8.4
6.15.9
6.15.9.1
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
600 SIPROTEC 5, Overcurrent Protection, Manual