Addr. Parameter C Setting Options Default Setting
_:2461:3 Supv. sum V:Threshold 0.300 V to 170.000 V 25.000 V
_:2461:6 Supv. sum V:Delay
supervision alarm
0.00 s to 100.00 s 5.00 s
VT miniatureCB
_:2641:101 VT minia-
tureCB:Response time
0.00 s to 0.03 s 0.00 s
Measuring Point V-1ph
Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Rated primary
voltage
0.200 kV to 1200.000 kV 400.000 kV
_:2311:102 General:Rated secondary
voltage
80 V to 340 V 100 V
_:2311:108 General:Matching ratio
Vph / VN
0.10 to 9.99 1.73
_:2311:103 General:Tracking
•
inactive
•
active
inactive
_:2311:130 General:Measuring-point
ID
0 to 100 0
VT 1
_:3811:103 VT 1:Magnitude correc-
tion
0.010 to 10.000 1.000
_:3811:108 VT 1:Phase
•
V A
•
V B
•
V C
•
V AB
•
V BC
•
V CA
•
VN
•
Vx
•
VCB
•
VN broken-delta
_:3811:107 VT 1:Sequence number
device
1 to 2147483647 2147483647
VT miniatureCB
_:2641:101 VT minia-
tureCB:Response time
0.00 s to 0.03 s 0.00 s
Information List
General
No.
Information Data Class
(Type)
Type
General
_:2311:500 General:>Phs-rotation reversal SPS I
_:2311:501 General:>Invert Phases SPS I
General
_:2311:319 General:Phase sequence ABC SPS O
_:2311:320 General:Phase sequence ACB SPS O
6.1.9
Protection and Automation Functions
6.1 Power-System Data
318 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017