Addr. Parameter C Setting Options Default Setting
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:110 User curve #:Reset
•
instantaneous
•
disk emulation
disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
Information List
No. Information Data Class
(Type)
Type
User curve #
_:81 User curve #:>Block stage SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate ACT O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O
Fast Stage
Description
Logic of a Stage
The fast stage is only available in function type Advanced.
6.12.5.4
6.12.6
6.12.6.1
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase
SIPROTEC 5, Overcurrent Protection, Manual 533
C53000-G5040-C017-8, Edition 07.2017