Addr. Parameter C Setting Options Default Setting
_:103 87N REF #:Threshold 0.05 I/IrObj to 2.00 I/IrObj 0.20 I/IrObj
_:105 87N REF #:Slope 0.00 to 0.95 0.07
_:109 87N REF #:Operate delay 0.00 s to 60.00 s; ∞ 0.00 s
_:191 87N REF #:Reference side is
•
not assigned
•
Side 1
•
Side 2
•
Side 3
•
Side 4
•
Side 5
not assigned
Information List
No. Information Data Class
(Type)
Type
87N REF #
_:82 87N REF #:>Block function SPS I
_:54 87N REF #:Inactive SPS O
_:52 87N REF #:Behavior ENS O
_:53 87N REF #:Health ENS O
_:55 87N REF #:Pickup ACD O
_:57 87N REF #:Operate ACT O
_:303 87N REF #:Operate delay expired ACT O
_:305 87N REF #:Block by direct. det. SPS O
_:306 87N REF #:I REF,operate MV O
_:307 87N REF #:I Angle,REF MV O
_:311 87N REF #:I REF,Trip operate MV O
_:312 87N REF #:I angle,REF operate MV O
_:301 87N REF #:I diff. MV O
_:302 87N REF #:I restr. MV O
6.43.6
Protection and Automation Functions
6.43 Restricted Ground-Fault Protection
SIPROTEC 5, Overcurrent Protection, Manual 879
C53000-G5040-C017-8, Edition 07.2017