Settings
Addr. Parameter C Setting Options Default Setting
V0>dir.harm.#
_:1 V0>dir.harm.#:Mode
off
on
test
off
_:2 V0>dir.harm.#:Operate
& flt.rec. blocked
no
yes
no
_:10 V0>dir.harm.#:Blk. by
meas.-volt. failure
no
yes
yes
_:106 V0>dir.harm.#:Direc-
tional mode
non-directional
forward
reverse
forward
_:103 V0>dir.harm.#:Forward
section +/-
0 ° to 90 ° 80 °
_:102 V0>dir.harm.#:V0>
threshold value
0.300 V to 200.000 V 20.000 V
_:201 V0>dir.harm.#:Harmonic
selection
3rd harmonic
5th harmonic
7th harmonic
5th harmonic
_:203 V0>dir.harm.#:Min. 3I0>
harmonic
1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:204 V0>dir.harm.#:3I0 harm.
dropout ratio
0.10 to 0.95 0.60
_:110 V0>dir.harm.#:Dir.-result
extension
0.00 s to 60.00 s 5.00 s
_:105 V0>dir.harm.#:Dir.
determination delay
0.00 s to 60.00 s 0.00 s
_:6 V0>dir.harm.#:Operate
delay
0.00 s to 60.00 s 1.00 s
Information List
No.
Information Data Class
(Type)
Type
V0>dir.harm.#
_:81 V0>dir.harm.#:>Block stage SPS I
_:501 V0>dir.harm.#:>Block delay & op. SPS I
_:54 V0>dir.harm.#:Inactive SPS O
_:52 V0>dir.harm.#:Behavior ENS O
_:53 V0>dir.harm.#:Health ENS O
_:303 V0>dir.harm.#:Ground fault ACD O
_:55 V0>dir.harm.#:Pickup ACD O
_:56 V0>dir.harm.#:Operate delay expired ACT O
_:57 V0>dir.harm.#:Operate ACT O
_:308 V0>dir.harm.#:Phi(I,V) harm. MV O
_:307 V0>dir.harm.#:V0 harm. MV O
6.15.9.3
6.15.9.4
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual 607
C53000-G5040-C017-8, Edition 07.2017