Siemens recommends using the default settings, which reflect common practice in Germany. Other national
transmission codes may require a slightly different range.
Parameter: Time delay
Default setting (_:13951:108) Time delay = 0.00 s
You use the Time delay parameter to specify the minimum time delay for releasing the reconnection of the
power-generation facility after tripping by protection.
The setting depends on the specific application.
Settings
Addr. Parameter C Setting Options Default Setting
Reclos. stage
_:13951:1 Reclos. stage:Mode
off
on
test
off
_:13951:101 Reclos. stage:V>
threshold value
3.000 V to 340.000 V 95.000 V
_:13951:104 Reclos. stage:f difference
positive
0.01 Hz to 5.00 Hz 0.05 Hz
_:13951:105 Reclos. stage:f difference
negative
-5.00 Hz to -0.01 Hz -2.50 Hz
_:13951:106 Reclos. stage:I> release
threshold
1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:13951:108 Reclos. stage:Time delay 0.00 s to 3600.00 s 0.00 s
_:13951:102 Reclos. stage:Configura-
tion
Setting options depend on
configuration
Information List
No.
Information Data Class
(Type)
Type
Reclos. stage
_:13951:81 Reclos. stage:>Block stage SPS I
_:13951:501 Reclos. stage:>V, f trip SPS I
_:13951:54 Reclos. stage:Inactive SPS O
_:13951:52 Reclos. stage:Behavior ENS O
_:13951:53 Reclos. stage:Health ENS O
_:13951:301 Reclos. stage:Release closure ACT O
6.40.4.3
6.40.4.4
Protection and Automation Functions
6.40 Undervoltage-Controlled Reactive-Power Protection