Siemens 7SJ85 - Directional Intermittent Ground-Fault Protection

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Directional Intermittent Ground-Fault Protection
Setting Values
Threshold
value 3I0>
For current transformer type
protection and I
rated
= 1 A
0.030 A to 35.000 A Increments of 0.001 A
For current transformer type
protection and I
rated
= 5 A
0.15 A to 175.00 A Increments of 0.01 A
For I
N
transformer
type sensitive and
I
N-rated
= 1 A
For I
ph-rated
= 1 A 0.001 A to 35.000 A Increments of 0.001 A
For I
ph-rated
= 5 A 0.001 A to 175.000 A Increments of 0.001 A
For I
N
transformer
type sensitive and
I
N-rated
= 5 A
For I
ph-rated
= 1 A 0.005 A to 35.000 A Increments of 0.001 A
For I
ph-rated
= 5 A 0.005 A to 175.000 A Increments of 0.001 A
Number of pulses until intermit-
tent ground fault
2 to 10 Increments of 1
Pickup extension time 0.00 s to 10.00 s Increments of 0.01 s
Sum of extended pickup times 0.00 s to 100.00 s Increments of 0.01 s
Reset time 1.00 s to 600.00 s Increments of 0.01 s
Number of pulses for operate 2 to 100 Increments of 1
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Times
Pickup time
Approx. 30 ms + OOT
90
at 50 Hz
Approx. 23 ms + OOT at 60 Hz
Dropout time Approx. 25 ms + OOT at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Active with less sensitivity
12.17
90
OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Technical Data
12.17 Directional Intermittent Ground-Fault Protection
1474 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017