Addr. Parameter C Setting Options Default Setting
_:17072:2 Stage 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:17072:3 Stage 2:Threshold 0.50 % to 100.00 % 15.00 %
_:17072:4 Stage 2:Dropout ratio 0.90 to 0.99 0.95
_:17072:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s
Information List
No. Information Data Class
(Type)
Type
Stage 1
_:17071:81 Stage 1:>Block stage SPS I
_:17071:54 Stage 1:Inactive SPS O
_:17071:52 Stage 1:Behavior ENS O
_:17071:53 Stage 1:Health ENS O
_:17071:55 Stage 1:Pickup ACD O
_:17071:56 Stage 1:Operate delay expired ACT O
_:17071:57 Stage 1:Operate ACT O
Stage 2
_:17072:81 Stage 2:>Block stage SPS I
_:17072:54 Stage 2:Inactive SPS O
_:17072:52 Stage 2:Behavior ENS O
_:17072:53 Stage 2:Health ENS O
_:17072:55 Stage 2:Pickup ACD O
_:17072:56 Stage 2:Operate delay expired ACT O
_:17072:57 Stage 2:Operate ACT O
6.28.4.4
Protection and Automation Functions
6.28 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage
SIPROTEC 5, Overcurrent Protection, Manual 733
C53000-G5040-C017-8, Edition 07.2017