Settings
Addr. Parameter C Setting Options Default Setting
Stage 1
_:331:1 Stage 1:Mode
•
off
•
on
•
test
off
_:331:2 Stage 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:331:10 Stage 1:Blk. by meas.-
volt. failure
•
no
•
yes
yes
_:331:109 Stage 1:Detection of
faulty phase
•
no
•
yes
no
_:331:8 Stage 1:Method of
measurement
•
fundamental comp.
•
fund. comp. long filter
•
RMS value
fundamental
comp.
_:331:3 Stage 1:Threshold 0.300 V to 200.000 V 30.000 V
_:331:4 Stage 1:Dropout ratio 0.90 to 0.99 0.95
_:331:107 Stage 1:Pickup delay 0.00 s to 320.00 s 0.00 s
_:331:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
_:331:101 Stage 1:V> healthy ph-
to-gnd volt.
0.300 V to 200.000 V 75.000 V
_:331:104 Stage 1:V< faulty ph-to-
gnd volt.
0.300 V to 200.000 V 40.000 V
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:331:81 Stage 1:>Block stage SPS I
_:331:54 Stage 1:Inactive SPS O
_:331:52 Stage 1:Behavior ENS O
_:331:53 Stage 1:Health ENS O
_:331:300 Stage 1:Faulty phase ACT O
_:331:55 Stage 1:Pickup ACD O
_:331:56 Stage 1:Operate delay expired ACT O
_:331:57 Stage 1:Operate ACT O
6.24.5
6.24.6
Protection and Automation Functions
6.24 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage
SIPROTEC 5, Overcurrent Protection, Manual 709
C53000-G5040-C017-8, Edition 07.2017