Prerouting 7SJ82/85 General
Meaning of the abbreviations in DIGSI, see 8.2.2.3 Connection Variants of the Circuit Breaker.
Binary Inputs
Table A-7 Default Binary Inputs, Using the Example of Overcurrent Protection
Binary
Input
Signal Number Signal Type Configura-
tion
BI1 Circuit breaker 1:Circuit break.:Position 201.4261.58 DPC OH
BI2 Circuit breaker 1:Circuit break.:Position 201.4261.58 DPC CH
BI3 Disconnector 1:Circuit break.:Position 601.5401.58 DPC OH
BI4 Disconnector 1:Circuit break.:Position 601.5401.58 DPC CH
BI5 Disconnector 2:Circuit break.:Position 602.5401.58 DPC OH
BI6 Disconnector 2:Circuit break.:Position 602.5401.58 DPC CH
BI7 Disconnector 3:Circuit break.:Position 603.5401.58 DPC OH
BI8 Disconnector 3:Circuit break.:Position 603.5401.58 DPC CH
BI9 Power system:Meas. point V-3ph 1:VT-
miniature CB:>Open
11.941.2641.500 SPS H
Binary Outputs
Table A-8
Default Output Relays, Using the Example of Overcurrent Protection
Binary
Output
Signal Number Signal Type Configura-
tion
BO1 Circuit breaker 1:Circuit break.:Trip/open
cmd.
201.4261.300 SPS U
BO2 Circuit breaker 1:Circuit break.:Close
command
201.4261.301 SPS X
BO3 Disconnector 1:Disconnector:Open
command
601.5401.300 SPS X
BO4 Disconnector 1:Disconnector:Close
command
601.5401.301 SPS X
BO5 Disconnector 2:Disconnector:Open
command
602.5401.300 SPS X
BO6 Disconnector 2:Disconnector:Close
command
602.5401.301 SPS X
BO7 Disconnector 3:Disconnector:Open
command
603.5401.300 SPS X
BO8 Disconnector 3:Disconnector:Close
command
603.5401.301 SPS X
Function Keys
Table A-9
Default Setting Function Key Using the Example of Overcurrent Protection
Function
Key
Signal Number Signal Type Configura-
tion
F-key1 Main menu:Logs:Operational log X
F-key2 Main menu:Measurements:VI 3ph
1:Operational values
X
F-key3 Main menu:Logs:Fault log X
A.10
Appendix
A.10 Prerouting 7SJ82/85 General
1610 SIPROTEC 5, Overcurrent Protection, Manual