Stage with Inverse-Time Overcurrent Protection, Voltage-Dependent
Description
Logic of the Stage
[lovoldep-210713-01.tif, 2, en_US]
Figure 6-26
Logic Diagram of the Inverse-Time Overcurrent Protection, Voltage-Dependent
Method of Measurement
You use the Method of measurement parameter to define whether the stage uses the
fundamental
comp.
(standard method) or the calculated
RMS value
.
6.4.3
6.4.3.1
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases
SIPROTEC 5, Overcurrent Protection, Manual 361