Addr. Parameter C Range of Values Default Setting
Side data
_:1781:14611:130 Side number
not assigned
Side 1
Side 2
Side 3
Side 2
_:1781:14611:210 MI3ph1 usesMeasP with ID 0 to 100 8
_:1781:14611:215 CT mismatch M I-3ph 1 0.010 to 100.000 1.000
Settings
Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:15571:101 General:Capacitor reference
curr.
1 A to 100 000 A 1000A
_:1781:15571:102 General:Capacitor reference
volt.
0.20 kV to1200.00 kV 400.00 kV
Side data
_:1781:15571:149 General:Neutral point
grounded
isolated
isolated
_:1781:15571:104 General:Winding configuration
Y (Wye)
D (Delta)
Y (Wye)
_:1781:15571:100 General:Vector group numeral 0 to 11 0
Measurements
_:1781:14611:158 Further settings:P, Q sign
not reversed
reversed
not reversed
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED Group
_:7381:500 Reset LED Group:>LED reset SPS I
_:7381:320 Reset LED Group:LED have been reset SPS O
5.5.3.5
5.5.3.6
Function-Group Types
5.5 Function-Group Type Capacitor Bank Differential Protection
236 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents