External Trip Initiation
Setting Values
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s
Times
Operate time with time delay = 0 ms
- At initiation via binary input signal
Approx. 10 ms + OOT
143
.
Tolerance
Sequence tolerance for delay times 1 % of the setting value or 10 ms
12.51
143
OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
Technical Data
12.51 External Trip Initiation
SIPROTEC 5, Overcurrent Protection, Manual 1541