EasyManua.ls Logo

Siemens 7SJ85 - Synchronization Function

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Synchronization Function
Operating Modes
Synchrocheck
Switching synchronous systems
Switching asynchronous systems
Switching synchronous/asynchronous systems with balancing commands
De-energized switching
Direct closing command
Balancing Voltage
Balancing Frequency
Setting Values
Supervision/Delay/Pulse times:
Max.durat. sync.process 0.00 s to 3 600.00 s or ∞ (ineffec-
tive)
Increments of 0.01 s
Supervision time de-energized
switching
0.00 s to 60.00 s Increments of 0.01 s
Closure delay 0.00 s to 60.00 s Increments of 0.01 s
T V pulse min/T f pulse min 0.01 s to 1.00 s Increments of 0.01 s
T V pulse max/T f pulse max 0.01 s to 60.00 s Increments of 0.01 s
T pause V/T pause f 0.01 s to 60.00 s Increments of 0.01 s
T close without balancing 1.00 s to 100.00 s Increments of 0.01 s
Voltage threshold values:
Upper voltage limit V
max
0.300 V to 340.000 V (phase-to-
phase)
Increments of 0.001 V
Lower voltage limit V
min
0.300 V to 340.000 V (phase-to-
phase)
Increments of 0.001 V
V<, for off-circuit conditions
V>, for voltage present
0.300 V to 170.000 V (phase-to-
phase)
0.300 V to 340.000 V (phase-to-
phase)
Increments of 0.001 V
Increments of 0.001 V
Differential values, changeover thresholds asynchronous/synchronous/balancing:
Voltage differences
V2 > V1; V2 < V1
0.000 V to 170.000 V Increments of 0.001 V
Frequency difference f2 > f1;
f2 < f1
0.000 Hz to 2.000 Hz (synchro-
nous)
0.000 Hz to 4.000 Hz (asynchro-
nous)
Increments of 0.001 Hz
Angle difference α2 > α1; α2 < α1
0
o
to 90
o
Increments of 1
o
Δf threshold ASYN <-> SYN 0.010 Hz to 0.200 Hz Increments of 0.001 Hz
Δf set point for balancing -1.00 Hz to 1.00 Hz Increments of 0.01 Hz
Δf for the kick pulse -1.00 Hz to 1.00 Hz Increments of 0.01 Hz
Adjustments of the sides:
Angle adjustment
0.0
o
to 360.0
o
Increments of 0.1
o
Voltage adjustment 0.500 to 2.000 Increments of 0.001
Circuit breaker
Closing time of the circuit breaker 0.01 s to 0.60 s Increments of 0.01 s
12.57
Technical Data
12.57 Synchronization Function
SIPROTEC 5, Overcurrent Protection, Manual 1547
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals