Settings
Addr. Parameter C Setting Options Default Setting
Cold-load PU
_:1 Cold-load PU:Mode
off
on
test
off
_:101 Cold-load PU:Operating
mode
I open
CB and I open
I open
_:102 Cold-load PU:Dropout
threshold current
1 A @ 100 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:103 Cold-load PU:Dropout
delay curr.crit.
1 s to 600 s 600 s
_:104 Cold-load PU:Dropout
delay CB closed
1 s to 21600 s 3600 s
_:105 Cold-load PU:Min. CB-
open time
0 s to 21600 s 3600 s
Information List
No.
Information Data Class
(Type)
Type
Cold-load PU
_:81 Cold-load PU:>Block stage SPS I
_:500 Cold-load PU:>Block fast dropout SPS I
_:501 Cold-load PU:>Activate cold-load SPS I
_:54 Cold-load PU:Inactive SPS O
_:52 Cold-load PU:Behavior ENS O
_:53 Cold-load PU:Health ENS O
_:300 Cold-load PU:Cold-load pickup SPS O
5.8.10
5.8.11
Function-Group Types
5.8 Process Monitor
300 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017