i
NOTE
The logged indications are preconfigured and cannot be changed!
The log, which is organized as a ring buffer, cannot be deleted by the user!
If you want to archive security-relevant information without loss of information, you must regularly
read this log.
You cannot route additional indication objects to the setting-history log.
Communication Log
The logging of the respective status such as ensuing faults, test and diagnosis operation, and communication
capacity utilizations is done for all hardware-based configured communication interfaces. Up to 500 indica-
tions can be stored in the communication log. Logging occurs separately for each communication port of the
configured communication modules.
Reading from the PC with DIGSI 5
Use the project-tree window to reach the communication logs of your SIPROTEC 5 device.
Online access → Device → Test suite → Communication module
Then select:
J:Onboard Ethernet → Communication log
The communication log is shown to you in the state last loaded from the device.
Before this, refresh the contents by clicking the update arrows in the headline.
[sccompuf-140912-01, 2, en_US]
Figure 3-14 Reading the Communication Log with DIGSI 5
Reading on the Device through the On-Site Operation Panel
To reach the communication log from the main menu, use the navigation keys on the on-site operation
panel.
Main Menu → Test & Diagnosis → Log → Communication log
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
3.1.5.7
System Functions
3.1 Indications
SIPROTEC 5, Overcurrent Protection, Manual 77