You use the Blk. by meas.-volt. failure parameter to control the behavior of the function when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:
•
The device-internal supervision function Measuring-voltage failure detection is configured and
switched on.
•
The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 9.3.4.1 Overview of Functions).
Parameter Value Description
yes
The protection function is blocked (= default setting). Siemens recommends
using the default setting.
no
The protection function is not blocked.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:10 General:Blk. by meas.-
volt. failure
•
no
•
yes
yes
_:2311:102 General:Measuring
window
1 cycles to 10 cycles 1 cycles
_:2311:101 General:Minimum
voltage V1
0.300 V to 60.000 V 5.000 V
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:300 General:Undervoltage blocking SPS O
_:2311:301 General:V2/V1 MV O
6.28.3.3
6.28.3.4
Protection and Automation Functions
6.28 Overvoltage Protection with Negative-Sequence Voltage/Positive-Sequence Voltage
SIPROTEC 5, Overcurrent Protection, Manual 729
C53000-G5040-C017-8, Edition 07.2017