Addr. Parameter C Setting Options Default Setting
_:62:2 Stage 2:Operate & flt.rec.
blocked
no
yes
no
_:62:3 Stage 2:Threshold 40.00 Hz to 70.00 Hz 47.50 Hz
_:62:6 Stage 2:Operate delay 0.00 s to 600.00 s 10.00 s
Stage 3
_:63:1 Stage 3:Mode
off
on
test
off
_:63:2 Stage 3:Operate & flt.rec.
blocked
no
yes
no
_:63:3 Stage 3:Threshold 40.00 Hz to 70.00 Hz 47.00 Hz
_:63:6 Stage 3:Operate delay 0.00 s to 600.00 s 10.00 s
Information List
No. Information Data Class
(Type)
Type
General
_:2311:300 General:Undervoltage blocking SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:61:81 Stage 1:>Block stage SPS I
_:61:54 Stage 1:Inactive SPS O
_:61:52 Stage 1:Behavior ENS O
_:61:53 Stage 1:Health ENS O
_:61:55 Stage 1:Pickup ACD O
_:61:56 Stage 1:Operate delay expired ACT O
_:61:57 Stage 1:Operate ACT O
Stage 2
_:62:81 Stage 2:>Block stage SPS I
_:62:54 Stage 2:Inactive SPS O
_:62:52 Stage 2:Behavior ENS O
_:62:53 Stage 2:Health ENS O
_:62:55 Stage 2:Pickup ACD O
_:62:56 Stage 2:Operate delay expired ACT O
_:62:57 Stage 2:Operate ACT O
Stage 3
_:63:81 Stage 3:>Block stage SPS I
_:63:54 Stage 3:Inactive SPS O
_:63:52 Stage 3:Behavior ENS O
_:63:53 Stage 3:Health ENS O
_:63:55 Stage 3:Pickup ACD O
_:63:56 Stage 3:Operate delay expired ACT O
_:63:57 Stage 3:Operate ACT O
6.33.6
Protection and Automation Functions
6.33 Underfrequency Protection
772 SIPROTEC 5, Overcurrent Protection, Manual