Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 User curve #:Mode
•
off
•
on
•
test
off
_:2 User curve #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:26 User curve #:Dynamic
settings
•
no
•
yes
no
_:27 User curve #:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:8 User curve #:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:3 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:113 User curve #:Threshold
(absolute)
1 A @ 100 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 100 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.000 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.000 A
_:110 User curve #:Reset
•
instantaneous
•
disk emulation
disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
_:115 User curve #:Additional
time delay
0.00 s to 60.00 s 0.00 s
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by
AR off/n.ready
•
no
•
yes
no
_:35 User curve #:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:29 User curve #:Effected by
AR cycle 1
•
no
•
yes
no
_:36 User curve #:Stage
blocked
•
no
•
yes
no
_:14 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:102 User curve #:Time dial 0.05 to 15.00 1.00
6.5.6.3
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
400 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017