Operating Mode Application and Setting Notes
Counter
The number of directional pulses is the determining operate
criterion. Thus do not set the value for parameter No. of
pulses for operate too small. Consider that a permanent
intermittent ground fault will cause many current pulses. If no
time-grading considerations are required, Siemens recommends
using a value in the range of 10 to 20.
Integrator and counter
The integrator and the counter are the determining operate
criteria while the counter criterion is only used for the direction
determination. The value for parameter No. of pulses for
operate to fulfill the directional criterion can be set to a rather
small value in the range of 3 to 5.
Parameter: Sum of extended PU times
Default setting (_:16291:106) Sum of extended PU times = 20.00 s
This parameter is only relevant in the operating mode Integrator and counter.
With the parameter Sum of extended PU times, you set the threshold value for the integrator. If the
integration reaches Sum of extended PU times, the stage operates if the
Pulse no. reached
signal
and the pickup state is present.
The parameter Sum of extended PU times represents one of the 5 selectivity criteria (ground-fault direc-
tion, pickup threshold, pickup extension time, reset time, and integrator threshold value) for coordination of
the relays on subordinate devices. It is comparable to the time grading of the overcurrent protection.
The Sum of extended PU times has the shortest summation time in the radial system for the device that
is closest to the intermittent ground fault and that picks up.
Parameter: Reset time
Default setting (_:16291:107) Reset time = 300 s
With the parameter Reset time, you can define the maximum interval between 2 adjacent ground faults. If
the interval is larger than the Reset time, the counter and integrator are reset.
The Reset time parameter must be much higher than the operate value of the Sum of extended PU
times.
Parameter: Operate & flt.rec. blocked
Default setting (_:16291:2) Operate & flt.rec. blocked = no
With the parameter Operate & flt.rec. blocked, you can block the operate indication, the fault
recording, and the fault log. In this case, a ground-fault log is created instead of the fault log.
Settings
Addr.
Parameter C Setting Options Default Setting
Stage 1
_:16291:1 Stage 1:Mode
off
on
test
off
_:16291:2 Stage 1:Operate &
flt.rec. blocked
no
yes
no
_:16291:10 Stage 1:Blk. by meas.-
volt. failure
no
yes
yes
_:16291:101 Stage 1:Directional
mode
forward
reverse
forward
6.14.5
Protection and Automation Functions
6.14 Directional Intermittent Ground-Fault Protection
560 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017