Directional Negative-Sequence Protection
Overview of Functions
The function Directional negative-sequence protection with current-independent time delay (ANSI 46)
serves as the backup short-circuit protection for unbalanced faults.
With the negative-sequence system, various supervision and protection tasks can be realized, for example:
Recording of 1 or 2-phase short circuits in the system with a higher sensitivity than in classic overcurrent
protection. The pickup value can be set under the rated object current.
Recording of phase conductor interruptions in the primary system and in the current-transformer secon-
dary circuits
Location of short circuits or reversals in the connections to the current transformers
Indication of unbalanced states in the energy system
Protection of electrical machines following unbalanced loads that are caused by unbalanced voltages or
conductor interruptions (for example, through a defective fuse)
Structure of the Function
The Directional negative-sequence protection with definite time delay function can be used in protection
function groups with 3-phase current and voltage measurement.
The function comes factory-set with 1 stage. A maximum of 6 tripping stages can be operated simultaneously
in the function.
[dwnspdir-271112-01.tif, 1, en_US]
Figure 6-156 Structure/Embedding of the Function
If the device is equipped with the Inrush-current detection function, the tripping stages can be stabilized
against tripping due to transformer-inrush currents.
Function Description
Stage Control
The following figure shows a stage control. It is available separately for each stage.
6.18
6.18.1
6.18.2
6.18.3
Protection and Automation Functions
6.18 Directional Negative-Sequence Protection
642 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017