[scfbudct, 1, en_US]
Figure 8-86
Parameterization Options of the User-Defined Function Block [Control]
Parameter: Check switching authority
Default setting (_:104) Check switching authority = yes
With the Check switching authority parameter, you determine whether the command source of
switching commands must be checked (see chapter 8.3.1 Command Checks and Switchgear Interlocking
Protection).
Parameter: Check if pos. is reached
Default setting (_:105) Check if pos. is reached = yes
With the Check if pos. is reached parameter, you check at a switching command whether the
switching direction equals the current position.
Parameter: Check swi.auth. for Mode
Default setting (_:150) Check swi.auth. for Mode = no
With the Check swi.auth. for Mode parameter, you specify whether the switching authority for the
command source must be checked when switching the controllable Mode (controllable) to the mode
On, Off, or Test. If you set the parameter Check swi.auth. for Mode to yes, the switching command
is only executed with appropriate switching authority (see chapter 8.3.1 Command Checks and Switchgear
Interlocking Protection).
Settings
Addr.
Parameter C Setting Options Default Setting
U-def.FB ctl.#
_:104 U-def.FB ctl.#:Check
switching authority
no
yes
advanced
yes
_:105 U-def.FB ctl.#:Check if
pos. is reached
no
yes
yes
8.6.4
Control Functions
8.6 User-Defined Function Block [Control]
1178 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017