The selection list displays the measuring points that are connected to the I 3ph RLC interface of the Capacitor
bank function group:
[scmpselection_tolp_rlc, 1, en_US]
Figure 7-5 Example of Measuring-Point Selection
The MP selection parameter is set for all stages. The setting applies equally to all stages of the function.
In the default setting, a measuring point is not selected. You must select a measuring point. If you do not
select a measuring point, an inconsistency is indicated via the read-only parameter Consistency
failure :
[scinconsistency_tolp_rlc, 1, en_US]
Figure 7-6 Function Inconsistency Indication
Parameter: Rated-current selection
Default setting (_:2311:101) Rated-current selection = prim. rated curr.of MP
With the parameter Rated-current selection, you define the reference value for current normalization
in thermal-replica calculation, for percentage-measured values, and for thresholds set in percentages.
Parameter Value
Description
prim. rated curr.of MP
Select this setting if you want to use the rated current of the whole capac-
itor bank as the reference value.
RLC rated current
Select this setting if you want to use the individual rated current of the RLC
object to be proteced (for example, a resistor or reactor) as the reference
value.
Parameter: RLC rated current
Default setting (_:2311:102) RLC rated current = 1000 A
With the parameter RLC rated current, you set the primary rated current of the respective protected
object which is usually a reactor or resistor branch within the capacitor-bank installation.
Settings
Addr.
Parameter C Setting Options Default Setting
General
_:2311:101 General:Rated-current
selection
prim. rated curr.of MP
RLC rated current
prim. rated
curr.of MP
7.3.5
Capacitor Bank Protection
7.3 Thermal Overload Protection for Capacitor Banks
SIPROTEC 5, Overcurrent Protection, Manual 975
C53000-G5040-C017-8, Edition 07.2017