Siemens 7SJ85 - Application and Setting Notes for 1 Cycle of the Cyclic Automatic Reclosing Function

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
You can find detailed information about this functionality in the chapter 6.45.4.14 Closing Indication and
Close Command .
Application and Setting Notes for 1 Cycle of the Cyclic Automatic Reclosing
Function
For the function of the cyclic automatic reclosing function, 1 cycle is preset. The preset cycle cannot be
deleted. You can add and delete more cycles from the function library in DIGSI 5.
Parameter: Start from idle state allow.
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with action time.
Default setting (_:6571:102) Start from idle state allow. = yes
With the parameter Start from idle state allow. you can determine whether the action time of this
automatic reclosing cycle is started, if the automatic reclosing function is in idle state during with incoming
general pickup. Please set the parameter always to yes , if the automatic reclosing function is configured for
only 1 cycle. If several cycles are configured, you can control the effectiveness of the automatic reclosing
cycles with this parameter and various action times.
Detailed information about the functionality can be found in Chapters 6.45.4.6 Cycle Control with Operating
Mode 1: With Tripping/With Action Time und 6.45.4.7 Cycle Control with Operating Mode 2: With Pickup/With
Action Time.
Parameter: Action time
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with action time.
Default setting (_:6571:103) Action time = 0.2 s
With this parameter Action time you can determine, within which time frame the trip command must
appear, in order to start the automatic reclosing function. If the trip command occurs only after the action
time has expired, automatic reclosing does not occur within the active automatic reclosing cycle.
You can find detailed information about the functionality in
Chapters 6.45.4.6 Cycle Control with Operating Mode 1: With Tripping/With Action Time and 6.45.4.7 Cycle
Control with Operating Mode 2: With Pickup/With Action Time.
Parameter: Dead time aft. 3-pole trip
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with tripping.
Default setting (_:6571:108) Dead time aft. 3-pole trip = 0.5 s
With this parameter Dead time aft. 3-pole trip , you can determine after which dead time the auto-
matic reclosing function will be executed. After a 3-pole trip of the circuit breaker, the system stability is
priority. Since the switched off line cannot develop synchronizing forces, only a short dead time is permitted in
most cases. The usual duration is 0.3 s to 0.6 s. A longer period can be tolerated if a synchrocheck is carried
out prior to reclosing. Longer 3-pole dead times are also possible in radial systems.
Parameter: Dead time aft.1ph. pickup, Dead time aft.2ph. pickup, Dead time aft.3ph. pickup
This parameter is only important and can be set if you use the automatic reclosing function in an operating
mode with pickup.
Default setting (_:6571:104) Dead time aft.1ph. pickup = 1.2 s
Default setting (_:6571:105) Dead time aft.2ph. pickup = 1.2 s
Default setting (_:6571:106) Dead time aft.3ph. pickup = 0.5 s
6.45.8
Protection and Automation Functions
6.45 Automatic Reclosing Function
930 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017