[dw_pecinv-230813, 2, en_US]
Figure 7-32
Inverse-Time Characteristic Curve
Phase-Segregated Operate Indications
In contrast to what normally occurs in a 3-phase protection device, the function generates phase-segregated
operate indications. These indications are needed for supervision applications.
Function Values
Values
Description Primary Secondary % Referenced to
(_:2311:301) VpeakA Peak voltage phase A kV V Parameter Capacitor
reference volt./√3
(_:2311:302) VpeakB Peak voltage phase B kV V Parameter Capacitor
reference volt./√3
(_:2311:303) VpeakC Peak voltage phase C kV V Parameter Capacitor
reference volt./√3
You can find the parameter Capacitor reference volt. of the preceding table in the function block
General of the function group Capacitor bank.
Application and Setting Notes
Parameter: Capacitor rated current
Default setting (_:2311:101) Capacitor rated current = 1000.0 A
With the Capacitor rated current parameter, you set the primary rated current I
C-rated
of the capacitor
or the capacitor bank.
Keep in mind that the rated current of the capacitor considers harmonics in addition to the fundamental