Addr. Parameter C Setting Options Default Setting
Dyn.s: Cold load PU
_:8341:33 Inverse-T 1:Effect. b.
cold-load pickup
•
no
•
yes
no
_:8341:40 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:8341:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:106 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Dyn.set: bin.input
_:8341:34 Inverse-T 1:Effected by
binary input
•
no
•
yes
no
_:8341:41 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:8341:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:107 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:501 General:>Test of direction SPS I
_:2311:301 General:Test direction ACD O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:8161:81 Inverse-T 1:>Block stage SPS I
_:8161:501 Inverse-T 1:>Release delay & op. SPS I
_:8161:84 Inverse-T 1:>Activ. dyn. settings SPS I
_:8161:500 Inverse-T 1:>Block delay & op. SPS I
_:8161:54 Inverse-T 1:Inactive SPS O
_:8161:52 Inverse-T 1:Behavior ENS O
_:8161:53 Inverse-T 1:Health ENS O
_:8161:60 Inverse-T 1:Inrush blocks operate ACT O
_:8161:62 Inverse-T 1:Dyn.set. AR cycle1act. SPS O
_:8161:63 Inverse-T 1:Dyn.set. AR cycle2act. SPS O
_:8161:64 Inverse-T 1:Dyn.set. AR cycle3act. SPS O
_:8161:65 Inverse-T 1:Dyn.set. ARcycl.>3act SPS O
_:8161:66 Inverse-T 1:Dyn.set. CLP active SPS O
6.6.5.4
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, Overcurrent Protection, Manual 427
C53000-G5040-C017-8, Edition 07.2017