Parameter: Term. 1,3,5,7 in dir. of obj.
Default setting (_:2311:116) Term. 1,3,5,7 in dir. of obj. = yes
With the Term. 1,3,5,7 in dir. of obj. parameter, you define the direction of the current. If you set
the parameter Term. 1,3,5,7 in dir. of obj. = yes, the direction of the current to the protected
object is defined as
forward
.
Parameter: Magnitude correction
Default setting (_:3841:103) Magnitude correction = 1.000
When using the Magnitude correction parameter, you adjust the magnitude (magnitude correction) for
the current input. This allows you to correct the tolerances of the primary current transformer phase-selec-
tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.
i
i
NOTE
The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.
Application and Setting Notes for Measuring Point Voltage 3-Phase (V-3ph)
Settings for the supervision functions are also located in the voltage measuring point. You can find the
description of these settings in chapter Supervision Functions.
Parameter: Rated primary voltage
Default setting (_:8911:101) Rated primary voltage = 400.000 kV
The Rated primary voltage parameter is used to set the primary rated voltage of the voltage trans-
former.
Parameter: Rated secondary voltage
Default setting (_:8911:102) Rated secondary voltage = 100 V
The Rated secondary voltage parameter is used to set the secondary rated voltage of the voltage trans-
former.
Parameter: Matching ratio Vph / VN
Default setting (_:8911:103) Matching ratio Vph / VN = 1.73
With the parameter Matching ratio Vph / VN, you set the deviation between the calculated zero-
sequence voltage and the residual voltage measured directly via a measuring input. The different transmission
ratio of the voltage transformers is the cause for the deviation (see Figure 6-3).
The Matching ratio Vph / VN is equal to the ratio 3V
0 sec
/V
N sec
with
V
0 sec
Calculated zero-sequence voltage
V
N sec
Measured residual voltage
The zero voltage is calculated as phase-to-ground voltages. The residual voltage is measured on the broken-
delta winding of the voltage transformer. For 1-phase voltage transformers, the residual voltage is measured
in the generator or the transformer neutral point.
6.1.6
Protection and Automation Functions
6.1 Power-System Data
SIPROTEC 5, Overcurrent Protection, Manual 307
C53000-G5040-C017-8, Edition 07.2017