Parameter: Duration of V-seal-in time
Default setting (_:104) Duration of V-seal-in time = 4.00 s
The parameter Duration of V-seal-in time limits the pickup seal-in induced by an overcurrent or
undervoltage. The value must be set higher than the value of the parameter Operate delay. The difference
shall be greater than 0.5 s. In the default setting, a difference of 1 s is used.
Parameter: Vph-ph< threshold
Default setting (_:105) Vph-ph< threshold = 60.000 V
With the parameter Vph-ph< threshold, you can set the threshold at which the output signal
Voltage
release
is activated when the minimum phase-to-phase voltage falls below this threshold.
Parameter: V2> threshold
Default setting (_:106) V2> threshold = 4.600 V
With the parameter V2> threshold, you can set the threshold at which the output signal
Voltage
release
is issued when V2 exceeds the threshold.
Settings
Addr. Parameter C Setting Options Default Setting
Vseal-in+Vrel#
_:1 Vseal-in+Vrel#:Mode
off
on
test
off
_:2 Vseal-in+Vrel#:Operate
& flt.rec. blocked
no
yes
no
_:3 Vseal-in+Vrel#:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.350 A
5 A @ 100 Irated 0.150 A to 175.000 A 6.750 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.350 A
5 A @ 50 Irated 0.150 A to 175.000 A 6.750 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.350 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.750 A
_:6 Vseal-in+Vrel#:Operate
delay
0.00 s to 60.00 s 3.00 s
_:10 Vseal-in+Vrel#:Blk. by
meas.-volt. failure
no
yes
yes
_:101 Vseal-in+Vrel#:State of
V-seal-in
off
on
off
_:102 Vseal-in+Vrel#:V-seal-in
threshold
0.300 V to 175.000 V 46.200 V
_:104 Vseal-in+Vrel#:Duration
of V-seal-in time
0.10 s to 60.00 s 4.00 s
_:105 Vseal-in+Vrel#:Vph-ph<
threshold
0.300 V to 175.000 V 60.000 V
_:106 Vseal-in+Vrel#:V2>
threshold
0.300 V to 200.000 V 4.600 V
6.4.6.3
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases
376 SIPROTEC 5, Overcurrent Protection, Manual