EasyManua.ls Logo

Siemens 7SJ85 - 3-Phase Measuring-Voltage Failure

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-Phase Measuring-Voltage Failure
Logic
[losymmet-190912-01.tif, 1, en_US]
Figure 9-7
Logic Diagram 3-Phase Measuring-Voltage Failure
Balanced Fault – VA, VB, VC <
A 3-phase measuring-voltage failure is detected if the following criteria are fulfilled simultaneously:
All 3 phase-to-ground voltages drop below the threshold value 3ph.fail. - VA,VB,VC <
A jump of the voltage (Signal jump V)
If these criteria are fulfilled and the monitoring is released and not blocked, the 3ph.failure-alarm indica-
tion is output. When the voltage returns (even as 1-phase), the monitoring drops out.
Release by Phase Current
When all phase currents exceed the threshold value 3ph.fail. - phs.curr.release the monitoring is
released.
Blocking in the Case of a System Incident
In the case of a 3-phase system incident, supervision must be blocked. The device detects a 3-phase incident
with a jump in the current. This change is detected via the internal signal Jump I or when the change in
current of a phase current exceeds the threshold value 3ph.fail. - phs.curr. jump. The change in
9.3.2.4
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual 1247
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals