Addr. Parameter C Setting Options Default Setting
Spontan.indic.
_:139 General:Fault-display
with pickup
with trip
with pickup
Test support
_:150 General:Activate device
test mode
0
1
false
_:151 General:Oper.bin.outp.
under test
0
1
false
Information List
No. Information Data Class
(Type)
Type
General
_:510 General:>Test mode on SPS I
_:511 General:>Test mode off SPS I
_:507 General:>Device funct.logoff on SPS I
_:508 General:>Dev. funct.logoff off SPS I
_:512 General:>LED reset SPS I
_:52 General:Behavior ENS O
_:53 General:Health ENS O
_:51 General:Test mode ENC C
_:321 General:Protection on SPC C
_:54 General:Protection inactive SPS O
_:323 General:LED reset SPC C
_:320 General:LED have been reset SPS O
Settings-Group Switching
Overview of Functions
For different applications you can save the respective function settings in so-called Settings groups, and if
necessary enable them quickly.
You can save up to 8 different settings groups in the device. In the process, only one settings group is active at
any given time. During operation, you can switch between settings groups. The source of the switchover can
be selected via a parameter.
You can switchover the settings groups via the following alternatives:
Via the on-site operation panel directly on the device
Via an online DIGSI connection to the device
Via binary inputs
Via a communication connection to the substation automation technology.
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC 61850, DNP or Modbus TCP can be
used for switching the settings groups.
A settings group includes all switchable settings of the device. Except for a few exceptions (for example,
general device settings such as rated frequency), all device settings can be switched.
Detailed information about the settings groups can be found in the Operating Manual and DIGSI 5 Online
Help.