Addr. Parameter C Setting Options Default Setting
_:2311:103 General:Core balance
CT- current 1
1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:2311:104 General:Core balance
CT- current 2
1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:2311:105 General:CT angle error at
I1
0.0 ° to 5.0 ° 0.0 °
_:2311:106 General:CT angle error at
I2
0.0 ° to 5.0 ° 0.0 °
Informationen
No. Information Data Class
(Type)
Type
General
_:2311:302 General:Ground fault ACD O
_:2311:303 General:Flt. extinction det. SPS O
_:2311:309 General:Pos. measuring window SPS O
_:2311:301 General:Phi(I,V) MV O
Directional 3I0 Stage with Cos φ or Sin φ Measurement
Description
Logic
[logfp3i0stufe-280314-01.vsd, 1, en_US]
Figure 6-125 Logic Diagram of the Stage Control
6.15.3.4
6.15.4
6.15.4.1
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
568 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017