Parameter: Down integration time
Default setting (_:13861:102) Down integration time = 3.00 min
Use the parameter Down integration time in order to determine the duration until the internal integra-
tion value is linearly reduced from 100 % to 0 %.
For example, if the integration value is 52 %, a duration of 52 % × down integration time is required until the
integration value 0 % is reached. When using this parameter, the preloading of a capacitor can be considered
and therefore released quicker.
If you are knowledgeable about recovery time of stressed capacitors, they can be considered with this param-
eter.
Parameter: Dropout delay
Default setting (_:13861:7) Dropout delay = 1.00 s
The parameter Dropout delay can be used to prevent resetting of the integral value in the event that the
measured value briefly falls below the dropout threshold.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Capacitor rated
current
1.0 A to 100000.0 A 1000.0 A
Inverse-T 1
_:13861:1 Inverse-T 1:Mode
off
on
test
off
_:13861:2 Inverse-T 1:Operate &
flt.rec. blocked
no
yes
no
_:13861:103 Inverse-T 1:Dropout prin-
ciple
with dropout delay
with down integration
with down inte-
gration
_:13861:3 Inverse-T 1:Threshold 0.80 p.u. to 3.00 p.u. 1.10 p.u.
_:13861:102 Inverse-T 1:Down inte-
gration time
1 min to 1500 min 3 min
_:13861:7 Inverse-T 1:Dropout
delay
0.00 s to 3600.00 s 1.00 s
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:301 General:VpeakA MV O
_:2311:302 General:VpeakB MV O
_:2311:303 General:VpeakC MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:13861:81 Inverse-T 1:>Block stage SPS I
_:13861:54 Inverse-T 1:Inactive SPS O
_:13861:52 Inverse-T 1:Behavior ENS O
_:13861:53 Inverse-T 1:Health ENS O