EasyManua.ls Logo

Siemens 7SJ85 - Directional Negative-Sequence Protection with Definite-Time Delay

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Directional Negative-Sequence Protection with Definite-Time
Delay
Setting Values
Directional mode Forward, backward, non-directional
Stabilization with phase currents 0 % to 30 % Increments of 1 %
Threshold value (pickup value) at I
N-rated
= 1 A 0.030 A to 35.000 A Increments of 0.001 A
Threshold value (pickup value) at I
N-rated
= 5 A 0.15 A to 175.00 A Increments of 0.01 A
Extension time of the blocking after a 1-pole pause 0.00 s to 60.00 s Increments of 0.01 s
Setting Values for Direction Determination
Minimum negative-sequence system voltage V2 0.150 V to 20.000 V Increments of 0.001 V
Minimum negative-sequence system
current I2
For I
rated
= 1 A 0.030 A to 10.000 A Increments of 0.001 A
For I
rated
= 5 A 0.15 A to 50.00 A Increments of 0.01 A
Upper limit angle forward, β
0
o
to 360
o
Increments of 1
o
Lower limit angle forward, α
0
o
to 360
o
Increments of 1
o
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
Dropout differential of 3 % of the object rated current
Times
Operate time with time delay = 0 ms
Approx. 40 ms + OOT
109
at 50 Hz
Approx. 40 ms + OOT at 60 Hz
Dropout time Approx. 39 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Inactive
Tolerances
Threshold values:
Negative-sequence voltage V2 1 % of the setting value or 0.5 V
Negative-sequence current I2 2 % of the setting value or 10 mA at I
rated
= 1 A
1 % of the setting value or 5 mA at I
rated
= 5 A
Times:
Independent time delays 1 % of the setting value or 10 ms
12.21
109
OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Technical Data
12.21 Directional Negative-Sequence Protection with Definite-Time Delay
1492 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals