Settings
Addr. Parameter C Setting Options Default Setting
Rated values
_:14641:101 General:Capacitor refer-
ence curr.
1 A to 100000 A 1000 A
_:14641:102 General:Capacitor refer-
ence volt.
0.20 kV to 1200.00 kV 400.00 kV
Cap.bank data
_:14641:106 General:Capacitor
element type
•
fused
•
unfused
fused
_:14641:107 General:Blk.cls.cmd.dur.
discharge
•
off
•
on
off
_:14641:108 General:Discharge time 1 s to 1200 s 300 s
_:14641:109 General:Cap.-bank
neutral point
•
grounded
•
isolated
isolated
Measurements
_:14611:158 Further settings:P, Q
sign
•
not reversed
•
reversed
not reversed
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Reset LED Group
_:7381:500 Reset LED Group:>LED reset SPS I
_:7381:320 Reset LED Group:LED have been reset SPS O
General
_:14641:500 General:>Compensate SPS I
_:14641:501 General:>Reset comp. val. SPS I
_:14641:300 General:Blocked by discharge SPS O
_:14641:302 General:Discharge SPS O
_:14641:301 General:Cap.bank device status SPC C
5.4.5
5.4.6
Function-Group Types
5.4 Function-Group Type Capacitor Bank
SIPROTEC 5, Overcurrent Protection, Manual 223
C53000-G5040-C017-8, Edition 07.2017