Figure 10-3
Setting with DIGSI, General Settings, Pulse-Metered Values
Application and Setting Notes for Pulse-Metered Values
The functionality Pulse-metered values is not preconfigured. If you want to use the functionality, you must
load it from the library into the respective function group.
The parameters can be set individually for every pulse counter. You will find the setting parameters in DIGSI in
the project tree under Parameter > Function group
For pulse-metered values, the following described settings and binary inputs are available.
Parameter: Restore time
Default setting: (_:101) Restore time = none
Parameter Value
Description
none Deactivated
hh:00
Transfer on the full hour
hh:15
Transfer 15 minutes after the full hour Note:
hh:30
Transfer 30 minutes after the full hour Note:
hh:45
Transfer 45 minutes after the full hour Note:
Note: If the parameter is activated through a time setting, the parameter Restore interval is not in effect
and will be deactivated automatically.
Parameter: Restore interval
Default setting: (_:102) Restore interval = 0 min
10.8.2
Measured Values, Energy Values, and Supervision of the Primary System
10.8 User-Defined Metered Values
SIPROTEC 5, Overcurrent Protection, Manual 1323
C53000-G5040-C017-8, Edition 07.2017