EasyManua.ls Logo

Siemens 7SJ85 - Prerouting 7 SJ82;85 Capacitor Bank Applications

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Prerouting 7SJ82/85 Capacitor Bank Applications
Meaning of the abbreviations in DIGSI, see8.2.2.3 Connection Variants of the Circuit Breaker
Binary Inputs
Table A-11 Default Binary Inputs, Using the Example of Overcurrent Protection
Binary input Signal Number Signal type Configuration
BI1 Circuit breaker
1:Circuit
break.:Position
201.4261.58 DPC OH
BI2 Circuit breaker
1:Circuit
break.:Position
201.4261.58 DPC CH
Binary Outputs
Table A-12 Default Output Relays, Using the Example of Overcurrent Protection
Binary output Signal Number Signal type Configuration
BO1 Circuit breaker
1:Circuit
break.:Trip/open
cmd.
201.4261.300 SPS U
BO2 Circuit breaker
1:Circuit
break.:Close
command
201.4261.301 SPS X
Function Keys
Table A-13
Default Setting Function Key Using the Example of Overcurrent Protection
Function key Signal Number Signal type Configu-ration
F-key1 Main
menu:Logs:Opera-
tional log
X
F-key2 Main menu:Meas-
urements :Capacitor
bank 1:Operational
values
X
F-key3 Main
menu:Logs:Fault log
X
Light-Emitting Diodes
Table A-14
Default LED Displays, Using the Example of Overcurrent Protection
LEDs Signal Number Signal type Configura-tion
LED1 Capacitor bank 1:Group
indicat.:Pickup:phs A
SPS NT
LED2 Capacitor bank 1:Group
indicat.:Pickup:phs B
SPS NT
A.11
Appendix
A.11 Prerouting 7SJ82/85 Capacitor Bank Applications
1612 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents