EasyManua.ls Logo

Siemens 7SJ85 - Undervoltage Protection with 3-Phase Voltage

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Undervoltage Protection with 3-Phase Voltage
Setting Values for Stage Type Definite-Time Undervoltage Protection
Measured value Phase-to-phase
Phase-to-ground
Method of measurement Fundamental component
RMS value
Current-flow criterion On
Off
Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold value
128
0.300 V to 175.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 1.01 to 1.20 Increments of 0.01
Setting Values for Stage Type Inverse-Time Undervoltage Protection
Measured value Phase-to-phase
Phase-to-ground
Method of measurement Fundamental component
RMS value
Current-flow criterion On
Off
Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold 0.300 V to 175.000 V Increments of 0.001 V
Pickup factor 0.80 to 1.00 Increments of 0.01
Characteristic constant k 0.00 to 300.00 Increments of 0.01
Characteristic constant α 0.010 to 5.000 Increments of 0.001
Characteristic constant c 0.000 to 5.000 Increments of 0.001
Time multiplier 0.05 to 15.00 Increments of 0.01
Additional time delay 0.00 s to 60.00 s Increments of 0.01 s
Reset time 0.00 s to 60.00 s Increments of 0.01 s
Operate Curve
T
op
=T
Inv
+T
add
Where:
T
op
Operate delay
T
Inv
Inverse-time delay
T
add
Additional time delay (parameter Additional time delay)
12.36
128
If you have selected the Method of measurement = RMS value, do not set the threshold value under 10 V.
Technical Data
12.36 Undervoltage Protection with 3-Phase Voltage
1518 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017