You can use the Dropout delay parameter ≠ 0 s to obtain a uniform dropout behavior if you use it
together with an electromechanical relay. This is required for time grading. The dropout time of the electro-
mechanical relay must be known for this purpose. Subtract the dropout time of your own device (see Tech-
nical Data) and set the result.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:102 General:Rotation angle
of ref. volt.
-180 ° to 180 ° 45 °
General
_:8131:1 Definite-T 1:Mode
off
on
test
off
_:8131:2 Definite-T 1:Operate &
flt.rec. blocked
no
yes
no
_:8131:105 Definite-T 1:Directional
mode
forward
reverse
forward
_:8131:8 Definite-T 1:Method of
measurement
fundamental comp.
RMS value
fundamental
comp.
_:8131:107 Definite-T 1:Non-direc-
tional pickup
no
at volt.< & mem.empty
at volt.< &
mem.empty
_:8131:104 Definite-T 1:Directional
comparison
no
yes
no
_:8131:106 Definite-T 1:Release via
input signal
no
yes
no
_:8131:10 Definite-T 1:Blk. by
meas.-volt. failure
no
yes
yes
_:8131:26 Definite-T 1:Dynamic
settings
no
yes
no
_:8131:27 Definite-T 1:Blk. w.
inrush curr. detect.
no
yes
no
_:8131:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:4 Definite-T 1:Dropout
ratio
0.90 to 0.99 0.95
_:8131:101 Definite-T 1:Dropout
delay
0.00 s to 60.00 s 0.00 s
_:8131:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR off/n.rdy
_:8131:28 Definite-T 1:Effect. by AR
off/n.ready
no
yes
no
_:8131:35 Definite-T 1:Stage
blocked
no
yes
no
Dyn.set: AR cycle 1
_:8131:29 Definite-T 1:Effected by
AR cycle 1
no
yes
no
6.6.4.3
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
416 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017