EasyManua.ls Logo

Siemens 7SJ85 - Method Stage; Description

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2P-Method Stage
Description
Logic of the Stage
[LoCBW2PS, 2, en_US]
Figure 10-35
Logic of the 2P-Method Stage
Determination of the Tripping/Opening Current Value
For the description to determine the tripping/opening current value, refer to chapter 10.12.4.1 Description.
Calculation of Remaining Switching Cycles
A double-logarithmic diagram provided by the circuit-breaker manufacturer illustrates the relationship of
permitted switching cycles and the tripping/opening current, see the following figure. According to the
example, this circuit breaker can operate approximately 1000 times at a tripping current of 10 kA.
2 points and their connecting line determine the relationship of switching cycles and tripping current. Point P1
is determined by the number of permitted switching cycles at rated normal current I
rated
. Point P2 is deter-
10.12.5
10.12.5.1
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring
1360 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals