EasyManua.ls Logo

Siemens 7SJ85 - Page 1361

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
mined by the maximum number of switching cycles at rated short-circuit breaking current I
sc
. The 4 associated
values can be configured with the parameters Rated normal current, Switching cycles at Ir,
Rated short-circ.cur. Isc, and Switching cycles at Isc.
[DwCBWOpC, 1, en_US]
Figure 10-36
Diagram of Switching Cycles for the 2P Method
As shown in the preceding figure, a double-logarithmic diagram, the straight line between P1 and P2 can be
expressed by the following exponential function:
[FoCBW2P1-301012-01.tif, 1, en_US]
Where:
I
trip
Tripping/opening current
I
rated
Rated normal current
m Slope coefficient
b Switching cycles at rated normal current
n Number of switching cycles
The general line equation for the double-logarithmic representation can be derived from the exponential func-
tion and leads to the coefficients b and m.
Measured Values, Energy Values, and Supervision of the Primary System
10.12 Circuit-Breaker Wear Monitoring
SIPROTEC 5, Overcurrent Protection, Manual 1361
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals