Addr. Parameter C Setting Options Default Setting
_:16291:102 Stage 1:Pickup mode
•
with 3I0>
•
with direction
with 3I0>
_:16291:103 Stage 1:Operating mode
•
Counter
•
Integrator and counter
Counter
_:16291:3 Stage 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:16291:105 Stage 1:Pickup extension
time
0.00 s to 10.00 s 0.10 s
_:16291:104 Stage 1:No.of pulses for
interm.GF
2 to 10 3
_:16291:106 Stage 1:Sum of
extended PU times
0.00 s to 100.00 s 20.00 s
_:16291:107 Stage 1:Reset time 1.00 s to 600.00 s 300.00 s
_:16291:108 Stage 1:No. of pulses for
operate
2 to 100 5
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:16291:81 Stage 1:>Block stage SPS I
_:16291:54 Stage 1:Inactive SPS O
_:16291:52 Stage 1:Behavior ENS O
_:16291:53 Stage 1:Health ENS O
_:16291:55 Stage 1:Pickup ACD O
_:16291:302 Stage 1:Stabilized pickup ACD O
_:16291:303 Stage 1:Limited pickup (log) ACD O
_:16291:304 Stage 1:Intermittent gnd.flt. SPS O
_:16291:301 Stage 1:Sum limit reached SPS O
_:16291:308 Stage 1:Pulse no. reached SPS O
_:16291:305 Stage 1:Reset time running SPS O
_:16291:57 Stage 1:Operate ACT O
_:16291:306 Stage 1:3I0 max. MV O
_:16291:310 Stage 1:Forward pulses MV O
_:16291:311 Stage 1:Reverse pulses MV O
_:16291:312 Stage 1:Non-dir. pulses MV O
6.14.6
Protection and Automation Functions
6.14 Directional Intermittent Ground-Fault Protection
SIPROTEC 5, Overcurrent Protection, Manual 561
C53000-G5040-C017-8, Edition 07.2017