Application and Setting Notes for the Stage
Parameter: External trip initiation
Default setting (_:14551:9) External trip initiation = no
With the External trip initiation parameter, you set whether an external input signal is used to
trigger the stage.
Parameter Value Description
no
The stage does not operate with an external input signal.
current
The stage operates with an external input signal.
If the stage operates with an external input signal, the binary input signal
>External current
must be routed in the DIGSI 5 information routing.
In this setting option, the binary input signal
>External current
is only
visible in the DIGSI 5 information routing
light
The stage operates with an external input signal.
If the stage operates with an external input signal, the binary input signal
>External light
must be routed in the DIGSI 5 information routing. In
this setting option, the binary input signal
>External light
is only
visible in the DIGSI 5 information routing
Note: When working with the light external trip initiation, do not select a
channel. If an additional channel is selected with this setting value, the
DIGSI 5 will signal an inconsistency.
Parameter: Operating mode
Default setting (_:14551:8) Operating mode = current and light
With the Operating mode parameter, you define the basic functionality of the stage.
Parameter Value
Description
current and light
The stage operates with the input variables current and light.
The current-flow criterion ensures that the light signal originates from an
arc.
Siemens recommends using this setting value.
light only
This stage operates only with the input signal 'light' and is triggered even if
current is not measured.
This operating mode can cause a overfunction if light is detected suddenly.
Use this setting value only if the effect caused by external light signals is
impossible.
Parameter: Sensor
Default setting (_:14551:11) Sensor = point sensor
With the Sensor parameter, you set which sensor type is connected to the device.
Parameter Value
Description
point sensor
A point sensor is connected to the device.
line sensor
A line sensor is connected to the device.
custom
If you select this setting option, the parameter Threshold light is
visible.
Siemens recommends the default setting values point sensor or line
sensor. This allows arcs to be detected reliably regardless of diffused light.
Parameter: Threshold light
Default setting (_:14551:7) Threshold light = -20.00 dB
6.10.5
Protection and Automation Functions
6.10 Arc Protection
504 SIPROTEC 5, Overcurrent Protection, Manual