EasyManua.ls Logo

Siemens 7SJ85 - Stage with Inverse-Time Characteristic Curve

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tolerances
Pickup value
I
2
/I
rated, obj
Approx. 2 % of the setting value
or 0.8 % of the absolute value
I
2
/I
1
Approx. 2 % of the setting value
or 4 % of the absolute value (I
1
> 50 mA
(I
rated
= 1 A) or 250 mA (I
rated
= 5 A))
Time delays 1 % of the setting value or 10 ms
Stage with Inverse-Time Characteristic Curve
Setting Values
Reference value for I
2
(I
ref
) Rated object current I
rated,obj.
Positive-sequence current I
1
Pickup value 5.0 % to 999.9 % l
2
/l
ref
Increments of 0.1
Dropout Disk emulation
Instantaneous
Time multiplier 0.05 to 15.00 Increments of 0.01
Release current (minimum
current release)
1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Maximum phase current
(maximum current
limiting)
1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
Dropout differential of 3 % of the object rated current
Times
Pickup time
Approx. 40 ms + OOT
108
at 50 Hz
Approx. 35 ms + OOT at 60 Hz
Dropout time Approx. 35 ms + OOT
Dropout Ratio
Disk emulation
Approx. 0.90 ⋅ threshold value
Instantaneous Approx. 1.05 ⋅ threshold value
Approx. 0.95 ⋅ pickup value
12.20.2
108
OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Technical Data
12.20 Negative-Sequence Protection
SIPROTEC 5, Overcurrent Protection, Manual 1489
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals