Addr. Parameter C Setting Options Default Setting
Supervis. grp. end
_:108 Superv.Grp.#:I/O module
ID
I/O module 1
I/O module 2
I/O module 3
I/O module 4
I/O module 5
I/O module 6
I/O module 7
I/O module 8
I/O module 9
I/O module 10
I/O module 11
I/O module 12
I/O module 13
I/O module 14
I/O module 15
I/O module 1
_:109 Superv.Grp.#:Binary
input
1 to 256 1
Information List
No. Information Data Class
(Type)
Type
Superv.Grp.#
_:52 Superv.Grp.#:Behavior ENS O
_:55 Superv.Grp.#:Sig. volt. disturbed SPS O
Voltage-Transformer Circuit Breaker
Overview of Functions
The Voltage-transformer circuit breaker function detects the tripping of the voltage-transformer circuit
breaker due to short circuits in the voltage-transformer secondary circuits.
The Voltage-transformer circuit breaker function works independently of Measuring-voltage failure detec-
tion and should be used – if possible – in parallel to it.
The tripping of the voltage-transformer circuit breaker has an impact on the quality of the recorded measured-
value data (see chapter 3.3 Processing Quality Attributes).
The following protection function is automatically blocked in cases of the tripping of the voltage-transformer
circuit breaker:
Directional negative-sequence protection
For the following functions the reaction (block/not block) can be set within the function in cases of a tripping
of the voltage-transformer circuit breaker:
Directional time-overcurrent protection, phases
Directional time-overcurrent protection, ground
Directional sensitive ground-fault detection
Overvoltage protection with negative-sequence voltage
Overvoltage protection with zero-sequence voltage/residual voltage
Undervoltage protection with 3-phase voltage
Undervoltage protection with positive-sequence voltage
9.3.3.6
9.3.4
9.3.4.1
Supervision Functions
9.3 Supervision of the Secondary System
1256 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017