Figure 8-32
Activating Additional Options of the Switching Authority
The additional parameters allow you to set the following options:
Specific sw.auth. valid for (for station/remote, only remote or only station):
With this parameter, you determine for which command source the extended switching-authority check
is used.
Table 8-21
Result Derived from the Combination of the Parameter Value Specific sw.auth. valid
for and the Level of the Command Source (Field Originator/orCat of the Switching
Command)
Command Source
Specific sw.auth. valid for
station station/remote remote
Local, local automatic No check No check No check
Station, station automatic Check Check No check
Remote, remote auto-
matic
No check Check Check
DIGSI No check No check No check
Control Functions
8.3 Control Functionality
1112 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017